9 | Electrical installation
Installer reference guide
103
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Capacity – Power
supply
F1B X14M
3kW 1N~ 230V
6kW 1N~ 230V
1N~ , 50 Hz
230 V AC
F1B.2+4
F1B.6+8
L N
Q3DI
6kW 3N~ 400V
9kW 3N~ 400V
L1 L2 NL3
3N~ , 50 Hz
400 V AC
Q3DI
F1B.6
F1B.8
L3
F1B.4
L2
F1B.2
L1 N
3 Fix the cable with cable ties to the cable tie mountings.
During connection of the backup heater, miswiring is possible. To detect possible
miswiring, it is highly recommended to measure the resistance value of the heater
elements. Depending on the capacity and power supply, following resistance
values (see table below) should be measured. ALWAYS measure the resistance on
the contactor clamps K1M, K2M, and K5M.
3kW
1N~ 230V
6kW
1N~ 230V
6kW
3N~ 400V
9kW
3N~ 400V
K1M/1 K5M/13 52.9Ω 52.9Ω ∞ ∞
K1M/3 ∞ 105.8Ω 105.8Ω 105.8Ω
K1M/5 ∞ 158.7Ω 105.8Ω 105.8Ω
K1M/3 K1M/5 26.5Ω 52.9Ω 105.8Ω 105.8Ω