11 | Configuration
Installer reference guide
154
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
If room buffering is enabled, the extra energy from photovoltaic panels is buffered
in the DHW tank and in the space heating/cooling circuit (i.e. heat up or cool down
the room). With the room comfort setpoints (cooling/heating) you can modify the
maximum/minimum setpoints that will be used when buffering the extra energy in
the space heating/cooling circuit.
# Code Description
[1.9.1] [9-0A] Heating comfort setpoint
▪ [3-07]~[3-06]°C
[1.9.2] [9-0B] Cooling comfort setpoint
▪ [3-09]~[3-08]°C
11.6.3 Main zone
Overview
The following items are listed in the submenu:
Main zone
Additional zone
Room
Malfunctioning
Space heating/cooling
[2] Main zone
Setpoint screen
[2.1] Schedule
[2.2] Heating schedule
[2.3] Cooling schedule
[2.4] Setpoint mode
[2.5] Heating WD curve
[2.6] Cooling WD curve
[2.7] Emitter type
[2.8] Setpoint range
[2.9] Control
[2.A] Thermostat type
[2.B] Delta T
[2.C] Modulation
[2.E] WD curve type
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone.
See "Setpoint screen"[4132].
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
▪ In Weather dependent LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.