9 | Electrical installation
Installer reference guide
107
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
To connect the bypass valve kit
The information in this topic supersedes that of the instruction sheet delivered
with the bypass valve kit.
Wires: 3×0.75mm²
The components of the bypass valve kit are as follows. You only need B and D.
A B
C D
1 Integrate components B and D as follows in the system:
B
D
FHL1
FHL2
FHL3
EKMBHBP1
B
D
Cu
A
18°C 0.25 m
0.5 m
0.1 m
0.2 m
Alpex
A
5°C
2 On the outdoor unit, connect B to the appropriate terminals as shown in the
illustration below.
X2M.4
X2M.3
N
Y
L
X2M.35
M4S
B