11 | Configuration
Installer reference guide
179
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
INFORMATION
Risk of space heating capacity shortage for domestic hot water tank without internal
booster heater: In case of frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when selecting the following:
Tank > Heat up mode > Reheat only.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
# Code Description
[5.7.1] [2‑01] Activation:
0: No
1: Yes
[5.7.2] [2‑00] Operation day:
0: Every day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
[5.7.3] [2‑02] Start time
[5.7.4] [2‑03] Tank setpoint:
55°C~75°C
[5.7.5] [2‑04] Duration:
5~60minutes
00.00 22.00 24.0001.00 23.00 t
T
DHW
T
H
T
U
[2-02]
[2-03]
[2-04]
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature
T
H
High setpoint temperature [2-03]
t Time