6 | Application guidelines
Installer reference guide
49
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Determining the volume and desired temperature for the DHW tank
Formula Example
V
1
=V
2
+V
2
×(T
2
−40)/(40−T
1
) If:
V
2
=180l
T
2
=54°C
T
1
=15°C
Then V
1
=280l
V
2
=V
1
×(40−T
1
)/(T
2
−T
1
) If:
V
1
=480l
T
2
=54°C
T
1
=15°C
Then V
2
=307l
V
1
DHW consumption (equivalent hot water volume at 40°C)
V
2
Required DHW tank volume if only heated once
T
2
DHW tank temperature
T
1
Cold water temperature
Possible DHW tank volumes
Type Possible volumes
Standalone DHW tank 150l
180l
200l
250l
300 l (polypropylene tank is
compatible with solar kit)
500l (compatible with solar kit)
Energy saving tips
If the DHW consumption differs from day to day, you can program a weekly
schedule with different desired DHW tank temperatures for each day.
The lower the desired DHW tank temperature, the more cost effective. By
selecting a larger DHW tank, you can lower the desired DHW tank temperature.
The heatpump itself can produce domestic hot water of maximum 55°C (lower if
the outdoor temperature is low). The electrical resistance integrated in the
heatpump can increase this temperature. However, this consumes more energy.
We recommend to set the desired DHW tank temperature below 55°C to avoid
using the electrical resistance.
The higher the outdoor temperature, the better the performance of the
heatpump.
- If energy prices are the same during the day and the night, we recommend to
heat up the DHW tank during the day.
- If energy prices are lower during the night, we recommend to heat up the DHW
tank during the night.