4/8
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with
default value
Setting name
└─ Disinfection
A.4.4.1 [2-01] R/W
0: No
1: Yes
A.4.4.2 [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3 [2-02] R/W 0~23 hour, step: 1 hour
23
A.4.4.4 [2-03] R/W fixed value
60°C
A.4.4.5 [2-04] R/W 40~60 min, step: 5 min
40 min
└─ Maximum setpoint
A.4.5 [6-0E] R/W [E-06]=1:
[E-07]
6:
40~75°C, step: 1°C, 75°C
[E-07]=6: 40~60°C, step: 1°C, 60°C
[E-06]=0:
40~65°C
,
ste
p
: 1°C
,
65°C
└─ SP mode
A.4.6 R/W
0: Fixed
1: Weather de
p
.
└─ Weather dependent curve
A.4.7 [0-0B] Weather-dependent curve DHW setpoint for high ambient temp. for DHW
WD curve.
R/W 35~[6-0E]°C, step: 1°C
55°C
A.4.7 [0-0C] Weather-dependent curve DHW setpoint for low ambient temp. for DHW
WD curve.
R/W 45~[6-0E]°C, step: 1°C
60°C
A.4.7 [0-0D] Weather-dependent curve High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.4.7 [0-0E] Weather-dependent curve Low ambient temp. for DHW WD curve. R/W -40~5°C, step: 1°C
-10°C
└─ Heat sources
└─ Boiler
A.5.2.2 [5-01] R/W -15~35°C, step: 1°C
5°C
└─ System operation
└─ Auto restart
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Pwr consumpt. Control
A.6.3.1 [4-08] R/W
0: No limitation
1: Continuous
2: Di
g
ital in
p
uts
A.6.3.2 [4-09] R/W
0: Current
1: Power
A.6.3.3 [5-05] R/W 0~50 A, step: 1 A
50
A
A.6.3.4 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1 [5-05] Amp. limits for DI Limit DI1 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.2 [5-06] Amp. limits for DI Limit DI2 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.3 [5-07] Amp. limits for DI Limit DI3 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.4 [5-08] Amp. limits for DI Limit DI4 R/W 0~50 A, step: 1 A
50
A
A.6.3.6.1 [5-09] kW limits for DI Limit DI1 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2 [5-0A] kW limits for DI Limit DI2 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3 [5-0B] kW limits for DI Limit DI3 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4 [5-0C] kW limits for DI Limit DI4 R/W 0~20 kW, step: 0,5 kW
20 kW
└─ Averaging time
A.6.4 [1-0A] R/W 0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Ext amb. sensor offset
A.6.5 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
└─ Savings mode
A.6.7 [7-04] R/W
0: Economical
1: Ecolo
g
ical
└─ Emergency
A.6.C R/W
0: Manual
1: Automatic
└─ Overview settings
A.8 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
60°C
A.8 [0-02] R/W 10~25°C, step: 1°C
15°C
A.8 [0-03] R/W
-40~5°C, step: 1°C
-10°C
A.8 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
8°C
A.8 [0-05] R/W [9-07]~[9-08]°C, step: 1°C
12°C
A.8 [0-06] R/W 25~43°C, step: 1°C
35°C
A.8 [0-07] R/W 10~25°C, step: 1°C
20°C
A.8 [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
A.8 [0-0C] R/W 45~[6-0E]°C, step: 1°C
60°C
Disinfection
Operation day
kW value
Start time
Temperature target
Duration
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Equilibrium temp.
Mode
Type
Amp. value
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
4P353731-1J - 2022.09