5/8
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with
default value
Setting name
A.8 [0-0D] R/W 10~25°C, step: 1°C
15°C
A.8 [0-0E] R/W -40~5°C, step: 1°C
-10°C
A.8 [1-00] R/W -40~5°C, step: 1°C
-10°C
A.8 [1-01] R/W 10~25°C, step: 1°C
15°C
A.8 [1-02] R/W
[9-01]~[9-00]°C, step: 1°C
60°C
A.8 [1-03] R/W [9-01]~min(45,[9-00])°C, step: 1°C
35°C
A.8 [1-04] R/W 0: Disabled
1: Enabled
A.8 [1-05] R/W 0: Disabled
1: Enabled
A.8 [1-06] R/W 10~25°C, step: 1°C
20°C
A.8 [1-07] R/W
25~43°C, step: 1°C
35°C
A.8 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C
A.8 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
18°C
A.8 [1-0A] R/W 0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8 [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.8 [2-01] R/W
0: No
1: Yes
A.8 [2-02] R/W 0~23 hour, step: 1 hour
23
A.8 [2-03] R/W fixed value
60°C
A.8 [2-04] R/W 40~60 min, step: 5 min
40 min
A.8 [2-05] R/W 4~16°C, step: 1°C
8°C
A.8 [2-06] R/W 0: Disabled
1: Enabled
A.8 [2-09] R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
A.8 [3-00] R/W 0: No
1: Yes
A.8 [3-01]
0
A.8 [3-02]
1
A.8 [3-03]
4
A.8 [3-04]
2
A.8 [3-05]
1
A.8 [3-06] R/W 18~30°C, step: A.3.2.4
30°C
A.8 [3-07] R/W 12~18°C, step: A.3.2.4
12°C
A.8 [3-08] R/W 25~35°C, step: A.3.2.4
35°C
A.8 [3-09] R/W 15~25°C, step: A.3.2.4
15°C
A.8 [4-00]
1
A.8 [4-01]
0
A.8 [4-02] R/W 14~35°C, step: 1°C
25°C
A.8 [4-03]
3
A.8 [4-04]
1
A.8 [4-05]
0
A.8 [4-06]
0/1
A.8 [4-07]
1
A.8 [4-08] R/W
0: No limitation
1: Continuous
2: Di
g
ital in
p
uts
A.8 [4-09] R/W 0: Current
1: Power
A.8 [4-0A]
0
A.8 [4-0B] R/W 1~10°C, step: 0,5°C
1°C
A.8 [4-0D] R/W 1~10°C, step: 0,5°C
3°C
A.8 [4-0E] Is the installer on site? R/W 0: No
1: Yes
A.8 [5-00]
0
A.8 [5-01] R/W -15~35°C, step: 1°C
5°C
A.8 [5-02]
0
A.8 [5-03]
0
A.8 [5-04]
10
A.8 [5-05] R/W 0~50 A, step: 1 A
50
A
A.8 [5-06] R/W 0~50 A, step: 1 A
50
A
A.8 [5-07] R/W 0~50 A, step: 1 A
50
A
A.8 [5-08] R/W 0~50 A, step: 1 A
50
A
Weather dependent cooling of the additional leaving water temperature zone.
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the disinfection target temperature?
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Is auto restart of the unit allowed?
--
--
--
--
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
What is the minimum desired room temperature in cooling?
--
--
Below which outdoor temperature is heating allowed?
--
--
--
-- (Do not change this value)
--
Which power limitation mode is required on the system?
Which power limitation type is required?
--
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
--
What is the equilibrium temperature for the building?
--
--
--
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
4P353731-1J - 2022.09