Loading...
Monobloc • EBHQ011-016AA6W1
•Altherma
TM
• Monobloc
186
4 Capacity tables
4 - 2 Cooling capacity tables
3
4
EBHQ011-016AA6W1
Maximum Cooling Capacity
Model
Tamb 20 25 30 35 40 45
LWE [°C]
CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW]
3TW58012-1A
SYMBOLS
CC : Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
HC : Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
PI : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
LWE : Leaving Water Evaporator temperature (°C)
LWC : Leaving Water Condensor temperature (°C)
Tamb : Ambient temperature (°C) RH=85%
(a) : only E(D/B)L*
NOTES
1 Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 38°C
Capacity values may not be extrapolated below 7°C leaving water temperature
2 Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 38°C
3 Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to
be added = 95W