• Outdoor units • ERHQ011-016AAW1
•Altherma
TM
• Outdoor units
56
2 Specifications
2
2
Motor Speed (nominal) Steps 8 8 8
Heating rpm 760 760 760
Cooling rpm 780 780 780
Fan Motor Output W 70 70 70
Drive Direct drive
Compressor Quantity 1 1 1
Motor Model JT1G-VDYR@S
Type Hermetically sealed scroll compressor
Motor Output W 2,200
Starting Method Inverter driven
Motor Crankcase Heater Output W 33 33 33
Operation Range Heating Min °CWB -20 -20 -20
Max °CWB 35 35 35
Cooling Min °CDB 10 10 10
Max °CDB 46 46 46
Sanitary water Min °CDB -20 -20 -20
Max °CDB 43 43 43
Sound Level
(nominal)
Heating Sound Power dBA 64 64 66
Sound
Pressure
dBA 51 51 52
Cooling Sound Power dBA 64 66 69
Sound
Pressure
dBA 50 52 54
Sound Level (Night
quiet)
Heating Sound
Pressure
dBA 42 42 43
Cooling Sound
Pressure
dBA 45 45 46
Refrigerant Type R-410A
Charge kg 2.95 2.95 2.95
Control Expansion valve(electronic type)
Nr of Circuits 1 1 1
Refrigerant Oil Type Daphne FVC68D
Charged Volume l 1.0 1.0 1.0
Piping connections Liquid (OD) Quantity 1 1 1
Type Flare connection
Diameter
(OD)
mm 9,52
Gas Quantity 1 1 1
Type Flare connection
Diameter
(OD)
mm 15,9
Drain Quantity 3 3 3
Type Hole
Diameter
(OD)
mm 26 26 26
Quantity 1 1 1
Type Hole
Diameter
(OD)
mm 18 18 18
Piping Length Minimum m 5 5 5
Maximum m 75 75 75
Equivalent
m95 95 95
Chargeless m 10 10 10
Additional Refrigerant Charge kg/m See installation manual outdoor unit 4PW42025-1
Installation height
difference
Maximum m 30 30 30
Heat Insulation Both liquid and gas pipes
Defrost Method Pressure equalising
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
2-2 TECHNICAL SPECIFICATIONS ERHQ011AAW1 ERHQ014AAW1 ERHQ016AAW1