•Altherma
TM
• Monobloc
105
• Monobloc • EDHQ011-016AA6W1
2 Specifications
3
2
2-1 NOMINAL CAPACITY AND NOMINAL INPUT EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1
Condition 1 Heating capacity Nominal kW 11.20 14.00 16.00
Heating PI Nominal kW 2.51 3.22 3.72
COP Nominal 4.46 4.35 4.30
Condition 2 Heating capacity Nominal kW 10.87 13.10 15.06
Heating PI Nominal kW 3.12 3.98 4.58
COP Nominal 3.48 3.29 3.29
Notes
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2 TECHNICAL SPECIFICATIONS EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1
Casing Colour Ivory white
Material Painted galvanised steel
Dimensions Unit Height mm 1,418
Width mm 1,435
Depth mm 382 382 382
Packing Height mm 1,557
Width mm 1,500
Depth mm 430 430 430
Weight Unit kg 180 180 180
Packed unit kg 200 200 200
Packing Material Wood
Carton
Plastic foil
Weight kg 20 20 20
Operation Range Heating - Ambient Min °CDB -15 -15 -15
Max °CDB 35 35 35
Heating - Waterside Min °C 15 15 15
Max °C 55 55 55
Domestic hot water
-Ambient
Min °CDB -15 -15 -15
Max °CDB 43 43 43
Domestic hot water
- Waterside
Min °C 25 25 25
Max °C 80 80 80
Sound Level
(nominal)
Heating Sound
Pressure
dBA 49 51 53
Sound Level (Night
quiet)
Heating Sound
Pressure
dBA 42 42 43
Refrigerant Type R-410A
Charge kg 2.95 2.95 2.95
Control Electronic expansion valve
Nr of Circuits 1 1 1
Refrigerant Oil Type Daphne FVC68D
Charged Volume l 1.0 1.0 1.0
Defrost Method Pressure equalising
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Safety Devices High pressure switch
Fan motor thermal protector
Fuse
Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee