Outdoor units • ERHQ006-008AD
•Altherma
TM
• Outdoor units
14
3 Capacity tables
3 - 1 Cooling/Heating capacity tables
1
3
COOLING
Model
Tamb (°C) 20 25 30 35 40 43
LWE (°C)
CC PI CC PI CC PI CC PI CC PI CC PI
006
7 6.01 1.56 5.73 1.75 5.43 1.95 5.12 2.16 4.80 2.39 4.59 2.53
11 6.81 1.57 6.50 1.77 6.17 1.98 5.83 2.21 5.30 2.32 4.98 2.38
13 7.23 1.57 6.90 1.78 6.56 2.00 6.20 2.23 5.56 2.28 5.18 2.30
16 7.88 1.56 7.54 1.78 7.17 2.01 6.79 2.26 5.95 2.22 5.46 2.18
20 8.80 1.55 8.42 1.79 8.03 2.03 7.63 2.29 6.48 2.13 5.82 1.99
007
7 7.15 2.05 6.84 2.28 6.50 2.52 6.13 2.77 5.35 2.68 4.89 2.59
11 8.09 2.09 7.73 2.34 7.34 2.59 6.94 2.87 5.84 2.62 5.21 2.43
13 8.57 2.11 8.20 2.36 7.79 2.63 7.36 2.91 6.09 2.59 5.36 2.34
16 9.33 2.13 8.92 2.40 8.49 2.68 8.03 2.97 6.46 2.53 5.57 2.20
20 10.4 2.16 9.9 2.44 9.48 2.73 8.99 3.04 6.96 2.44 5.82 1.99
008
7 8.24 2.43 7.90 2.68 7.52 2.94 7.10 3.23 5.68 2.86 4.87 2.59
11 9.26 2.49 8.87 2.76 8.45 3.05 7.79 3.31 6.12 2.80 5.18 2.43
13 9.79 2.52 9.38 2.80 8.93 3.10 8.14 3.36 6.34 2.77 5.33 2.35
16 10.6 2.57 10.17 2.86 9.69 3.17 8.68 3.41 6.67 2.71 5.55 2.20
20 11.7 2.63 11.3 2.94 10.75 3.26 9.39 3.48 7.09 2.61 5.80 1.99
HEATING (Peak values)
Model
LWC 30 35 40 45 50
Tamb
HC PI HC PI HC PI HC PI HC PI
006
-15 3.93 1.48 3.67 1.59 3.47 1.71 3.33 1.84 3.25 1.99
-10 4.65 1.52 4.32 1.65 4.07 1.79 3.89 1.94 3.78 2.10
-7 5.14 1.54 4.77 1.68 4.49 1.83 4.28 1.99 4.15 2.16
-2 6.06 1.57 5.62 1.72 5.28 1.88 5.03 2.06 4.87 2.25
2 6.89 1.57 6.38 1.74 6.00 1.91 5.72 2.11 5.53 2.31
7 8.03 1.57 7.45 1.75 7.00 1.94 6.68 2.15 6.47 2.37
007
-15 4.87 1.82 4.62 1.94 4.43 2.08 4.30 2.23 4.24 2.40
-10 5.67 1.88 5.34 2.02 5.09 2.18 4.92 2.36 4.82 2.55
-7 6.21 1.91 5.83 2.07 5.55 2.24 5.35 2.42 5.23 2.63
-2 7.23 1.95 6.77 2.13 6.42 2.32 6.17 2.52 6.02 2.75
2 8.14 1.97 7.61 2.16 7.21 2.37 6.92 2.59 6.74 2.83
7 9.40 1.98 8.79 2.19 8.32 2.42 7.98 2.66 7.78 2.92
008
-15 5.42 2.06 5.16 2.19 4.97 2.34 4.86 2.51 4.80 2.70
-10 6.27 2.13 5.93 2.29 5.68 2.46 5.51 2.65 5.42 2.86
-7 6.84 2.17 6.46 2.34 6.17 2.53 5.97 2.73 5.86 2.95
-2 7.92 2.22 7.45 2.41 7.10 2.62 6.85 2.85 6.70 3.10
2 8.9 2.26 8.35 2.46 7.93 2.69 7.65 2.93 7.47 3.20
7 10.2 2.28 9.58 2.51 9.10 2.76 8.76 3.02 8.56 3.31
H
EATING (integrated values*)
Model
LWC 30 35 40 45 50
Tamb
HC PI HC PI HC PI HC PI HC PI
006
-15 3.50 1.40 3.27 1.51 3.09 1.62 2.97 1.75 2.89 1.89
-10 4.14 1.45 3.85 1.56 3.62 1.70 3.46 1.84 3.36 2.00
-7 4.52 1.45 4.20 1.58 3.95 1.72 3.77 1.87 3.65 2.03
-2 5.27 1.46 4.89 1.60 4.59 1.75 4.38 1.92 4.24 2.10
2 5.92 1.45 5.49 1.60 5.16 1.76 4.92 1.94 4.76 2.13
7 8.03 1.57 7.45 1.75 7.00 1.94 6.68 2.15 6.47 2.37
007
-15 4.34 1.73 4.11 1.85 3.94 1.98 3.83 2.12 3.77 2.28
-10 5.04 1.79 4.75 1.92 4.53 2.07 4.38 2.24 4.29 2.42
-7 5.46 1.80 5.13 1.94 4.88 2.10 4.71 2.28 4.60 2.47
-2 6.29 1.81 5.89 1.98 5.59 2.15 5.37 2.35 5.23 2.56
2 7.00 1.81 6.55 1.99 6.20 2.18 5.96 2.38 5.80 2.61
7 9.40 1.98 8.79 2.19 8.32 2.42 7.98 2.66 7.78 2.92
008
-15 4.82 1.96 4.59 2.08 4.43 2.23 4.32 2.39 4.27 2.56
-10 5.58 2.03 5.28 2.17 5.06 2.34 4.91 2.52 4.82 2.72
-7 6.02 2.04 5.69 2.20 5.43 2.37 5.26 2.57 5.15 2.78
-2 6.89 2.07 6.48 2.25 6.17 2.44 5.96 2.65 5.83 2.88
2 7.6 2.08 7.18 2.27 6.82 2.47 6.58 2.70 6.43 2.94
7 10.2 2.28 9.58 2.51 9.10 2.76 8.76 3.02 8.56 3.31
* The integrated heating capacity and power
input, is the average heating capacity and
power input during 1 cycle. (from end of
defrost till end of the next defrost).
SYMBOLS
CC : Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
HC : Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
PI : Power input (kW)
LWE : Leaving Water Evaporator temperature (°C)
LWC : Leaving Water Condensor temperature (°C)
Tamb : Ambient temperature (°C) RH=85%
NOTES
1 Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 38°C
2 Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 38°C
3 Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 60 W (according EN14511).
For the optional model with heatertape (V38) when ambient temperature
becomes lower than 4°C: add power input of 60W
3TW57782-1A