EasyManua.ls Logo

Daikin Altherma EKHBH(X)016AB - Main Components

Daikin Altherma EKHBH(X)016AB
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Monobloc • EDHQ011-016AA6W1
•Altherma
TM
• Monobloc
106
2 Specifications
3
2
2-3 MAIN COMPONENTS EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1
Air heat exchanger Specifications Length mm 857 857 857
Nr of Rows 2 2 2
Fin pitch mm 1.4 1.4 1.4
Nr of Passes 5 5 5
Face area 1.131 1.131 1.131
Nr of Stages 60 60 60
Tube type Hi-XSS
Fin Type WF fin
Treatment Anti-corrosion treatment (PE)
Fan Type Propeller
Quantity 2 2 2
Discharge direction Horizontal
Motor Quantity 2 2 2
Model Brushless DC
Motor Speed (nominal) Steps 8 8 8
Heating rpm 760 760 760
Fan Motor Output W 70 70 70
Drive Direct drive
Compressor Quantity 1 1 1
Motor Model JT1G-VDYR@S
Type Hermetically sealed scroll compressor
Motor Output W 2,200
Starting Method Inverter driven
Motor Crankcase Heater Output W 33 33 33
Pump Type Water cooled
Nr. of speed 2 2 2
Nominal ESP unit Heating kPa 52.5 43.5 35.0
Power input W 210 210 210
Water side Heat
exchanger
Type Brazed plate
Quantity 1 1 1
Water volume l 1.01 1.01 1.01
Water flow rate Min. l/min 16 16 16
Water flow rate
Nom.
Heating l/min 32.1 40.1 45.9
Water flow rate Max. l/min 58 58 58
Insulation material Foamed synthetic elastomer
Expansion vessel Volume l 10 10 10
Maximum water pressure bar 3 3 3
Pre pressure bar 1.0 1.0 1.0
Water filter Diameter perforations mm 1 1 1
Material Brass
Water circuit Piping connections inch G5/4 (FEMALE)
Piping inch 5/4"
Safety valve bar 3 3 3
Manometer Yes
Drain valve / Fill valve yes
Shut off valve yes
Air purge valve yes
Total water volume (6) l 5.5 5.5 5.5

Table of Contents