SiUS181305E Other Control
Function 56
5. Other Control
5.1 Demand Control
In order to lower power consumption, the capacity of the outdoor unit is forcibly lowered using the
Demand 1 Setting.
To operate the unit with this mode, additional setting of Constant Demand Setting is necessary.
<Demand 1 setting>
Other protection control functions have precedence over the above operation.
5.2 Heating Operation Prohibition Control
Heating operation is prohibited when the outdoor temperature is above 24°CDB (75.2°FDB).
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%