EasyManua.ls Logo

Daikin DIII-NET - Adjusting Discharge Air Setpoint

Daikin DIII-NET
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 1133-C
DIII-NET COMMUNICATION GATEWAY 21 www.DaikinApplied.com
Figure 24, MicroTech III Air Handler in Unoccupied Operation
Adjusting Discharge Air Setpoint
Note: This only applies if ‘Std’ or ‘USw/Spt’ is selected for iTouch Version. Refer to DIII-Net Communication Gateway
Addressing section for more information.
Note: Discharge air temperature setpoint cannot be adjusted with ‘USw/oSpt’ selected.
1. Highlight the MicroTech III Air Handling unit and select Configure.
Figure 25, With MicroTech III Air Handling Unit Selected
2. For ‘Std’ select Modify for the setpoint. Change setpoint and press OK.
Configure Button

Table of Contents

Related product manuals