Test Procedures
If you can control the unit from its keypad, but you are not able to communicate with unit via the DIII network, follows these
steps:
Check the network wiring.
Check the network parameters and verify that they are correct, and that there are no duplicate devices on the network.
(Addresses must be unique.) See section “DIII Communication Gateway Addressing”
Verify that the MicroTech III controller is setup correctly. See section “Configuring the DIII Board and MicroTech III
Controller.”
If the DIII-NET Communication Gateway still does not respond, contact the Daikin Controls Customer Support Group
at 866-462-7829.