EasyManua.ls Logo

Daikin ERRQ 016AAY1 - U4 Malfunction of Transmission Indoor Unit

Daikin ERRQ 016AAY1
262 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE09-08 Troubleshooting by Indication on the Remote Controller
Troubleshooting 199
3.56 “U4” Malfunction of Transmission Indoor Unit
Remote Control
Display
U4
Subcode 4
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Microcomputer checks QA communication of indoor unit.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Wrong wiring between indoor unit PC boards. [A4P (1ø) or A5P (3ø)] and A1P
Troubleshooting
Caution
Replace indoor unit PC
board
Correct the wiring
YES
NO
Is the wiring
("1-2-3" communication
and upwiring)
normal?
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.

Table of Contents