SiBE121135 Code Indication on Remote Controller
Service Diagnosis 269
4.4 Outdoor Unit
i: ON, h: OFF, j: Blinks
Green : Blinks in normal condition
Red : OFF in normal condition
Note: 1. The error codes in the parenthesis ( ) are displayed only when the system is shut down.
2. When a sensor error occurs, check the remote controller display to determine which sensor
is malfunctioning.
If the remote controller does not indicate the error code, conduct the following procedure.
Turn the power switch off and back on again. If the same LED indication appears again
immediately after the power is turned on, the fault is in the thermistor.
If the above condition does not result, the fault is in the CT.
3. The indoor unit error code may take the precedence in the remote controller display.
4. 3-room models and 4-room models do not have LED5.
Outdoor Unit LED Indication Error Codes Description
Reference
Page
Green Red
A12345
jhhhhh00
Normal condition
UA
Unspecified voltage (between indoor unit and outdoor
unit)
301
UH
Anti-icing function in other rooms
301
jhhiih (U0)
Refrigerant shortage
296
jihhihU2
Low-voltage detection or over-voltage detection
298
jhiiihU7
Signal transmission error (on outdoor unit PCB)
300
jihiihA5
Anti-icing function
302
jiiihhE1
Outdoor unit PCB abnormality
304
jihihh (E5)
OL activation (compressor overload)
305
jhiihh (E6)
Compressor lock
306
jiiiihE7
DC fan lock
307
jhihihE8
Input overcurrent detection
308
jihihhF3
Discharge pipe temperature control
309
jihiihF6
High pressure control in cooling
310
jiihhhH0
Compressor sensor system abnormality
311
H6
Position sensor abnormality
313
H8
CT or related abnormality
315
H9
Outdoor temperature thermistor or related
abnormality
317
J3
Discharge pipe thermistor or related abnormality
317
J6
Outdoor heat exchanger thermistor or related
abnormality
317
J8
Liquid pipe thermistor or related abnormality
317
J9
Gas pipe thermistor or related abnormality
317
P4
Radiation fin thermistor or related abnormality
317
jiihihL3
Electrical box temperature rise
319
jhhhihL4
Radiation fin temperature rise
321
jhhihhL5
Output overcurrent detection
323