93 Trial Operation and Field Settings
2. Trial Operation
Outline Carry out the trial operation in accordance with the operation manual to ensure that all functions
and parts, such as flap movement, are working properly.
Trial operation should be carried out in either cooling or heating operation.
Detail 1. Measure the power supply voltage and make sure that it falls within the specified range.
2. In cooling operation, select the lowest programmable temperature (18°C); in heating
operation, select the highest programmable temperature (30°C).
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level (26°C ~ 28°C in
cooling, 20°C ~ 24°C in heating operation).
For protection, the system does not start for 3 minutes after it is turned off.
ARC466 Series
(1) Press the On/Off button to turn on the system.
(2) Press the center of the Temp button and the Mode button at the same time.
(3) Select
T
(trial operation) with the Temp or Temp button.
(4) Press the Mode button to start the trial operation.
(5) Press the Mode button and select operation mode.
(6) Trial operation terminates in approximately 30 minutes and switches into normal mode. To
quit trial operation, press the On/Off button.
(R19935)
(2) (4) (5)
(1) (6)
(2) (3)
(3)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK(X)M-P Series and is the answer not in the manual?

Daikin FTK(X)M-P Series Specifications

General IconGeneral
BrandDaikin
ModelFTK(X)M-P Series
CategoryHeat Pump
LanguageEnglish

Related product manuals