EasyManuals Logo

Daikin FTK(X)M-P Series User Manual

Daikin FTK(X)M-P Series
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
SiMT041509E Troubleshooting
Service Diagnosis 74
4.17 Compressor System Sensor Abnormality
Error Code
H0
Method of Error
Detection
The system checks the DC current before the compressor starts.
Error Decision
Conditions
The voltage converted from the DC current before compressor start-up is out of the range
0.5 ~ 4.5 V.
The DC voltage before compressor start-up is below 50 V.
Supposed
Causes
Broken or disconnected harness
Defective outdoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
(R22016)
YES
Turn off the power. Then, turn on
the power to restart the system.
YES
NO
Replace the harness.
Replace the outdoor unit
PCB (main PCB).
Is the harness broken?
Restart operation
and error displayed
again?
Check the relay harness for the
compressor.
Not a malfunction.
Keep observing.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK(X)M-P Series and is the answer not in the manual?

Daikin FTK(X)M-P Series Specifications

General IconGeneral
BrandDaikin
ModelFTK(X)M-P Series
CategoryHeat Pump
LanguageEnglish

Related product manuals