SiBE041029EC Forced Cooling Operation
Trial Operation and Field Settings 106
2. Forced Cooling Operation
Indoor Unit
Outdoor Unit: RX50/60G2V1B, 71 class
∗ The illustration is for 71 class as representative.
Outdoor Unit: RX50/60G2V1B9, RX50/60G3V1B, RX60G4V1B
Caution When pressing the button, do not touch the terminal board. It has a high voltage and may cause
electric shock.
Item Forced Cooling
Conditions The forced cooling operation is allowed when both of the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start The forced cooling operation starts when any of the following conditions are fulfilled.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit for 5
seconds.
2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor unit
within around 3 minutes after power is supplied.
Command
frequency
50/60 class: 66 Hz
71 class: 31 Hz
End The forced cooling operation ends when any of the following conditions are fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor unit.
Others Protection functions have priority over all other functions during forced cooling
operation.
Indoor unit ON/OFF button
(R19650)
LED-A
SW4
ON
ABCD
S102
SW1
S2
Forced cooling operation
ON/OFF button
(R19531)
1
2
3
Screwdriver
(R19532)
Forced cooling operation
ON/OFF button (SW1)
Push