EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
Troubleshooting by Remote Controller Si20-701_B
123
3.18
C6
Defective Combination
(between Indoor Unit PCB and
Fan PCB)
Remote Controller Display
C6
Applicable Models
FBQ, FMDQ-B7
Method of Error Detection
Conduct open line detection with fan PCB using indoor
unit PCB.
Error Decision Conditions
When the communication data of fan PCB is determined
as incorrect.
Supposed Causes
îš„ Defective fan PCB
îš„ Defective connection of capacity setting adaptor
îš„ Setting mistake on site

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals