EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #482 background imageLoading...
Page #482 background image
Troubleshooting by Remote Controller Si20-701_B
475
Check for Excessive Refrigerant Charging
As criteria for judging whether refrigerant is excessively
charged or not, refer to the following operating
conditions.
<Diagnosis of excessive refrigerant charging>
In cooling operation
(1) Because high pressure rises due to excessive
charging, overload control is carried out and capacity
tends to run short.
(2) Considering pressure load, compressor discharge
pipe temperature is low.
(3) Subcooling degree of condensate liquid becomes
large. Therefore, temperature of blown air passing
through subcooling part decreases in heating
operation.
CHECK 10

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals