EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
Si20-701_B Troubleshooting by Remote Controller
150
3.26
E3
High Pressure Abnormality
(HPS)
Remote Controller Display
E3
Applicable Models
RZQ-K/H, RZQ(S)-B/C, RZR-KU/HU
Method of Error Detection
The protection device circuit checks continuity in the high
pressure switch.
Error Decision Conditions
When the high pressure switch is actuated
Supposed Causes
îš„ Defective high pressure switch
îš„ Disconnection in high pressure switch harness
îš„ Defective connection of high pressure switch
connector
îš„ Clogged indoor unit suction filter (in heating)
îš„ Dirty outdoor unit heat exchanger
îš„ Defective outdoor unit fan
îš„ Refrigerant overcharge
îš„ Stop valve is not opened

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals