EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #255 background imageLoading...
Page #255 background image
Si20-701_B Troubleshooting by Remote Controller
248
3.50
J5
Suction Pipe Thermistor
Abnormality
Remote Controller Display
J5
Applicable Models
CMSQ
Method of Error Detection
The error is detected from the temperature detected by
the suction pipe thermistor.
Error Decision Conditions
When a short circuit or an open circuit in the suction pipe
thermistor is detected.
Supposed Causes
îš„ Defective thermistor for outdoor unit suction pipe
îš„ Defective outdoor unit PCB
îš„ Defective thermistor connection

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals