EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #263 background imageLoading...
Page #263 background image
Si20-701_B Troubleshooting by Remote Controller
256
3.54
JA
High Pressure Sensor
Abnormality
Remote Controller Display
JA
Applicable Models
RZQ, CMSQ
Method of Error Detection
The error is detected from the pressure detected by the
high pressure sensor.
Error Decision Conditions
When the high pressure sensor is short circuit or open
circuit
Supposed Causes
îš„ Defective high pressure sensor
îš„ Connection of low pressure sensor with wrong
connection
îš„ Defective outdoor unit PCB

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals