EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #466 background imageLoading...
Page #466 background image
Troubleshooting by Remote Controller Si20-701_B
459
3.110 Check
Check for Fan Motor Connector (Signal Line)
(1) Turn the power supply OFF.
For except FBQ
(2) With the fan motor connector disconnected, measure
the resistance between each pin, then make sure that
the resistance is more than the value mentioned in
the following table.
For FBQ
(2) With the fan motor connector disconnected, measure
the resistance between each pin, then make sure that
the resistance is balanced in ±30%.
CHECK 1
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
GND
Measurement
point
1 - 4
2 - 4
3 - 4
4 - 7
Judgement
1MΩ or more
100kΩ or more
100Ω or more
100kΩ or more
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc
Hw
HV
HU

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals