EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
Troubleshooting by Remote Controller Si20-701_B
79
3.4
A0
Error of External Protection
Device
Remote Controller Display
A0
Applicable Models
FCQ, FMCQ
Method of Error Detection
Detect open or short circuit between external input
terminals in indoor unit.
Error Decision Conditions
When an open circuit occurs between external input
terminals with the remote controller set to "external ON/
OFF terminal".
Supposed Causes
îš„ Actuation of external protection device
îš„ Improper field setting
îš„ Defective indoor unit PCB

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals