EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #324 background imageLoading...
Page #324 background image
Troubleshooting by Remote Controller Si20-701_B
317
3.72
LC
Transmission Error
Between Inverter and Control
PCB
Remote Controller Display
LC
Applicable Models
CMSQ, RZQ-C7
Method of Error Detection
Check the communication state between inverter PCB
and control PCB by micro-computer.
Error Decision Conditions
When the correct communication is not conducted in
certain period.
Supposed Causes
îš„ Connection error between the inverter PCB and
outdoor control PCB
îš„ Defective outdoor control PCB (transmission section)
îš„ Defective inverter PCB
îš„ Defective noise filter
îš„ Defective fan inverter
îš„ Incorrect type of fan inverter
îš„ Defective compressor
îš„ Defective fan motor
îš„ Address conflict on inverter PCB

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals