Troubleshooting by Remote Controller Si20-701_B
211
Troubleshooting
Is the
amount of
refrigerant
correct?
NO
YES
Charge with the
proper amount of
refrigerant.
Has
the thermistor
come off the
discharge pipe
port?
YES
NO
Correctly place
the discharge
pipe thermistor.
Is
electronic
expansion valve
fitted?
NO
YES
Is
electronic
expansion valve coil
disconnected from
valve body?
NO
YES
Check refrigerant
piping circuit
clogging.
Correctly place
the electronic
expansion valve
coil to valve
body.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.