EasyManuals Logo

Daikin FUY100FJV1 User Manual

Daikin FUY100FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #308 background imageLoading...
Page #308 background image
Troubleshooting by Remote Controller Si20-701_B
301
Troubleshooting
Output current check
YES
Is
the stop valve
open?
NO
YES
Open the stop
valve.
Check if the
compressor lead wires
are normal.
NO
YES
Replace the
compressor lead
wires.
Check
if the wiring
and connection to the
compressor are
normal.
NO
YES
Correct the
wiring and
connection.
Insulation
resistance of
the compressor is
100 kΩ or
below.
YES
NO
Replace the
inverter
compressor.
Compressor
coils are disconnected.
YES
NO
Replace the
inverter
compressor.
CHECK 16
Check if the power
transistor is
normal.
NO
Replace the
inverter PCB.
A
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Power OFF
Connect the compressor
lead wires then restart
the operation.

Table of Contents

Other manuals for Daikin FUY100FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY100FJV1 and is the answer not in the manual?

Daikin FUY100FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY100FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals