Troubleshooting by Remote Controller Si20-701_B
353
Troubleshooting
Refer to P.475.
Refer to P.477.
Is the stop
valve open?
NO
YES
Open the stop
valve.
Is the
refrigerant
amount appropriate?
NO
Collect
refrigerant.
After vacuum
drying is
complete, charge
an appropriate
amount of
refrigerant.
YES
Check the
refrigerant piping
system for
clogging.
CHECK 10
CHECK 11
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
CHECK 10
CHECK 11