ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 12 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 6: Multi-State Values - Ennity Single Stage Compressor, Continued
Point Name
Object
Type/
Instance
Read/
Write
Access
2
BACnet Object
Name
Range/Default
(in Units)
Non-
volatile
Memory
1
Description
MULTI-STATE VALUES
Auxiliary Heat Enable
Input
MSV:11 C AuxHeatEnable
1 to 3
Default: 3
N
Enables or disables auxiliary heat for units with electric heat.
Electric heat is always enabled when it is the only source
of heating, and is unaffected by this variable. The default
state is Null, in which case auxiliary heat is enabled. The
network override will revert back to its default value upon
unit controller reboot.
1 = Disabled
2 = Enabled
3 = Null
Energy Hold Off Input MSV:12 C EnergyHoldOff
1 to 3
Default: 3
N
When the unit is in the Energy Hold Off mode, the unit uses
Standby Setpoints. This command has priority over Effective
Occupancy.
7
The network override will revert back to its
default value upon unit controller reboot.
1 = Normal
2 = Energy Hold Off
3 = Null
Pump Request Output MSV:13 R PumpRequest 1 to 3 N
Indicates when the unit is requesting ow from the loop
water controller. The loop pump must be running to provide
adequate ow through the unit so the compressor(s) can
operate safely. MSV1 can be used by the BAS to indicate if
proper loop uid ow is occurring.
1 = No Request for Flow
2 = Request for Flow
3 = Null
Room Sensor
Setpoint Adjust
Enable/Disable
MSV:14 W cpLocSpEnable
1 to 2
Default: 2
Y
Enables or disables the Local Hardwired Setpoint
Adjustment. If the value of MSV14 is set to 1, this disables
the setpoint control from a room sensor and enables the
setpoint control from the BACnet network.
1 = Disabled
2 = Enabled
Units
(English/Metric)
MSV:15 W Units
1 to 2
Default: 1
Y
Both English and Metric units of measure for temperature
conversion are supported. This menu selection changes
the units for all the appropriate properties in the device.
From the network MSV15.Present_Value changes it.
Select either “E” for English; or “M” for Metric units from the
BACnet conguration menu. See BACnet Conguration and
Commissioning.
1 = English (E)
2 = Metric (M)

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals