ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 52 www.DaikinApplied.com
seleCTed parameTers InformaTIon
Binary Output Status
Table 24: Bit Description for Ennity Single Stage Compressor (Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, and
VHC/VHF)
Bit
Number
Bit Description Value Description
Unit Controller Outputs
0 Compressor #1 ON (1) Compressor #1 request
1 Fan or Fan Low Speed ON (1)
Fan request ON (single speed fan) or
Fan request at low speed (multispeed fan)
2 Reversing Valve #1
ON (1) Heating position for compressor #1
OFF (0) Cooling position for compressor #1
3 Pump Request/Isolation Valve ON (1) Water ow is required
4 Alarm Output (A – Terminal)
ON (1) Alarm output is energized with 24VAC when there is no fault
OFF (0) Alarm output is de-energized when there is a fault
5 Remote Circuit #1 – Red LED OFF (0) /ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate
unit controller Fault/Status mode for Circuit #1
6 Remote Circuit #1 – Green LED OFF (0)/ ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate
the unit controller Fault/Status mode for Circuit #1
7 Remote Circuit #1 – Yellow LED OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate
the unit controller Fault/Status mode for Circuit #1
8 Room Sensor Status LED
ON (1)
Indicates the room sensor Status LED is on Steady. LED is
ON when the unit controller is in either the Occupied or Bypass
modes
OFF (0)
Indicates the room sensor Status LED is either ashing or
constantly OFF
I/O Expansion Module Outputs
9 Compressor #2 or Fan Medium Speed ON (1) Compressor #2 request for fan request at medium speed
10 Reversing Valve #2 or Secondary Heating
ON (1)
Heating position for compressor #2 or Secondary Heating ON
request
OFF (0)
Cooling position for compressor #2 or Secondary Heating OFF
request
11 Hot Gas Reheat (HGR) ON (1) Hot Gas Reheat (HGR) request
12 Fan High Speed ON (1) Fan request at high speed
13 Remote Circuit #2 – Red LED OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate
the unit controller Fault/Status mode for Circuit #2
14 Remote Circuit #2 – Green LED OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate
the unit controller Fault/Status mode for Circuit #2
15 (MSB)
1
Remote Circuit #2 – Yellow LED OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate
the unit controller Fault/Status mode for Circuit #2
1. MSB = Most Signicant Bit