EasyManuals Logo

Daikin MicroTech I Sales And Engineering Data Sheet

Daikin MicroTech I
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 36 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 18: Network Variable Inputs (NVIs) - SmartSource Single and Two Stage Compressor and Ennity Large Two
Compressor, Continued
Point Name
lonWorks Variable
(NV Index
2
)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Variable Inputs (NVIs)
Energy Hold Off Input
nviEnergyHoldOff
(12)
SNVT_switch
(95)
Default: Null Recv
When the unit is in the Energy Hold Off mode, it uses
Standby setpoints. This command has priority over Effective
Occupancy.
3
The network override will revert back to its
default value upon unit controller reboot.
Selection State Value
Normal 0 NA
Normal 1 0%
HoldOff 1 0.5 to 100%
Null -1 0%
Fan ON/Auto
Remote Input
nviFanOnAuto
(15)
SNVT_switch
(95)
Default: Null No
Overrides the local fan ON/Auto room sensor and thermostat
switch inputs. The Fan Auto setting forces cycling fan mode.
Fan On forces the fan ON. The network override will revert
back to its default value upon unit controller reboot.
Selection State Value
Fan On 0 0%
Fan Auto 1 100%
Null -1 0 to 100%
Fan Runtime Totalizer
nviFanHours
(21)
SNVT_count
(8)
0 to 65535 counts
Default: 0
No Total fan runtime hours.
4
Humidistat Remote
Input
nviHumidistat
(16)
SNVT_switch
(95)
Default: Null No
Overrides the local humidistat/Stage #1 Cooling thermostat
input. The network override will revert back to its default value
upon unit controller reboot.
Selection State Value
No Dehumid Req 0 0%
Req Dehumid 1 100%
Null -1 0 to 100%
Occupancy
Override Input
nviOccManCmd
(13)
SNVT_occupancy
(109)
Default: OC_NUL No
Overrides the occupancy schedule. Occupancy Schedule
Override has priority over the Occupancy Schedule and
remote occupancy sensor. It is also allows a local timed
override hardwired to place the unit in the Occupied mode
during the amount of time declared in Timed Override
Setpoint using Schedule Override and/or an occupancy
sensor. The network override will revert back to its default
value upon unit controller reboot. See Effective Occupancy
Modes.
Supported Values
0 = OC_OCCUPIED
1 = OC_UNOCCUPIED
2 = OC_BYPASS
3 = OC_STANDBY
-1 (0xFF) = OC_NUL
Occupancy Scheduler
Input
nviOccSchedule
(17)
SNVT_tod_event
(128)
Default: OC_NUL Recv
Commands the WSHP into different occupancy modes. A
scheduler or a supervisory controller typically sends the
command using Schedule Override.
3
The network override
will revert back to its default value upon unit controller reboot.
See Effective Occupancy Modes.
Supported Current_state Values
0 = OC_OCCUPIED
1 = OC_UNOCCUPIED
3 = OC_STANDBY
-1 (0xFF) = OC_NUL
Next_state is not used
Time_to_next_state is not used
Occupancy
Sensor Input
nviOccSensor
(18)
SNVT_occupancy
(109)
Default: OC_NUL Recv
Indicates the presence of occupants in the space (motion
detection.)
3
The network override will revert back to its default
value upon unit controller reboot. See Effective Occupancy
Modes.
Supported Values
0 = OC_OCCUPIED
1 = OC_UNOCCUPIED
-1 (0xFF) = OC_NUL
1. Analog Null (0x7FFF) is a discrete temperature value of 621.806ºF/327.67ºC. Its purpose is to indicate a sensor failure condition or when the unit controller is not
using that temperature value.
2. The Network Variable index number is a unique identier for certain LonWorks variables. Some BAS companies use this numeric value instead of text to
reference these variables. The NV index number can also be found in the XIF le.
3. After Receive Heartbeat is enabled, this variable reverts to the default (non-override) value if it is not refreshed often enough through a network command or if
communication is disabled (i.e. the device is disabled or is ofine).
4. The totalizer continues to increment until the maximum count is reached, at which point the BAS must reset the value by issuing a write command. The variable is
saved in nonvolatile memory every 24 hours. If power is lost, that day’s totalizer information is not stored.

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals