effeCTIve oCCupanCy modes
www.DaikinApplied.com 57 ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
effeCTIve oCCupanCy modes
This section describes the relationship among the three
network occupancy inputs that determine the resulting effective
occupancy of the unit. Refer to Table 27 for BACnet and
Table 28 for LonWorks networks.
Table 27: Effective Occupancy Mode - BACnet
Local Sensor
Occupancy
Override
Input (MSV7)
Range: 1-5
Occupancy
Scheduler
Input (MSV8)
Range: 1–4
Occupancy
Sensor Input
(MSV9)
Range: 1–3
Effective
Occupancy
Output
(MSV6)
Range: 1–5
NA 1 (Occ) NA NA 1 (Occ)
NA 2 (Unoc) NA NA 2 (Unoc)
NA 3 (Bypass)
1 (Occ) NA 1 (Occ)
2 (Unoc) NA 3 (Bypass)
3 (Standby) NA 3 (Bypass)
4 (Null)
1 (Occ) 1 (Occ)
2 (Unoc) 2 (Unoc)
NA 4 (Standby) NA NA 4 (Standby)
NA 5 (Null)
1 (Occ)
1 (Occ) 1 (Occ)
2 (Unoc) 4 (Standby)
2 (Unoc) NA 2 (Unoc)
3 (Standby) NA 4 (Standby)
4 (Null)
1 (Occ) 1 (Occ)
2 (Unoc) 2 (Unoc)
Occ 5 (Null) 4 (Null) 3 (Null) 1 (Occ)
Unoc 5 (Null) 4 (Null) 3 (Null) 2 (Unoc)
Note: Refer to BACnet Network Objects for full BACnet name and descriptions.
Table 28: Effective Occupancy Mode - LonWorks
Local
Sensor
nviOccManCmd nviOccSchedule nviOccSensor nvoEffectOccup
NA OC_OCCUPIED NA NA OC_OCCUPIED
NA
OC_
UNOCCUPIED
NA NA
OC_
UNOCCUPIED
NA OC_BYPASS
OC_OCCUPIED NA OC_OCCUPIED
OC_
UNOCCUPIED
NA OC_BYPASS
OC_STANDBY NA OC_BYPASS
OC_NUL
OC_OCCUPIED OC_OCCUPIED
OC_
UNOCCUPIED
OC_
UNOCCUPIED
NA OC_STANDBY NA NA OC_STANDBY
NA OC_NUL
OC_OCCUPIED
OC_OCCUPIED OC_OCCUPIED
OC_
UNOCCUPIED
OC_STANDBY
OC_
UNOCCUPIED
NA
OC_
UNOCCUPIED
OC_STANDBY NA OC_STANDBY
OC_NUL
OC_OCCUPIED OC_OCCUPIED
OC_
UNOCCUPIED
OC_
UNOCCUPIED
OCC OC_NUL OC_NUL OC_NUL OC_OCCUPIED
UNOCC OC_NUL OC_NUL OC_NUL
OC_
UNOCCUPIED
Notes:
1. OC_BYPASS can be initiated by either nviOccManCmd or a local input.
nvoEffectOccup will only be OC_BYPASS for the duration of the Local Bypass Time
(nciBypassTime), until reinitiated by either a transition of the local input or an update to
nviOccManCmd.
2. The occupancy sensor can be either a local input or a network input. If a valid value
for the network input is present, it has precedence over a local input.
3. For the occupancy sensor, OC_NUL (and no local input) is interpreted as OC_
OCCUPIED.
4. For nviOccSchedule, this refers to the “current state” eld.
5. “Any State” = Any State.

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals