ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 62 www.DaikinApplied.com
appendIx a: proToCol ImplemenTaTIon ConformanCe sTaTemenTs (pICs)
appendIx a: proToCol ImplemenTaTIon ConformanCe sTaTemenTs (pICs)
BACnet PICS - Ennity Single Stage Compressor Water Source Heat
Pumps
This section contains the Protocol Implementation
Conformance Statement (PICS) for the MicroTech III WSHP
Unit Controller used with Ennity Single Stage Compressor
models: MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, and
VHC/VHF as required by ANSI/ASHRAE Standard 135-
2004, BACnet; A Data Communication Protocol for Building
Automation and Control Networks.
Protocol Implementation Conformance
Statement
Date: May 5, 2015
Vendor Name: Daikin Applied
Product Name: MTIIIUC_WSHP
Product Model Number: WSHP
Application Software
Version:
3.1
Firmware Revision: 3.2
BACnet Protocol Revision:
Version 1
Revision 4
Product Description
The MicroTech III WSHP unit controller with optional BACnet
communication module is a microprocessor designed to
operate the heat pump unit and integrate it into a BACnet
building automation system.
BACnet Standardized Device Prole
The MicroTech III WSHP unit controller supports the BACnet
Interoperability Building Blocks (BIBBS) included in the BACnet
Advanced Application Controller (B-AAC) prole. The following
section provides a complete listing of BIBBS.
BACnet Standardized Device Prole
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Specic Controller
(B-AAC)
BACnet Application Specic Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks
(BIBBS) Supported
BIBB Name Designation
Data Sharing – Read Property – B DS-RP-B
Data Sharing – Read Property Multiple – B DS-RPM-B
Data Sharing – Write Property – B DS-WP-B
Data Sharing – Write Property Multiple – B DS-WPM-B
Data Sharing – COV – B (15 Maximum Objects Supported) DS-COV-B
Device Management – Dynamic Device Binding – B DM-DDB-B
Device Management – Dynamic Object Binding – B DM-DOB-B
Device Management – Device Communication Control – B DM-DCC-B
Device Management – Time Synchronization – B DM-TS-B
Device Management – Reinitialize Device – B DM-RD-B

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals