ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 54 www.DaikinApplied.com
baCneT ConfIguraTIon and CommIssIonIng
BACnet Conguration
This section describes how to set BACnet parameters using
the BACnet communication module’s built-in conguration
menu (Figure 1). The BACnet conguration menu is accessed
using Microsoft Windows
®
HyperTerminal
®
or PuTTY. It is
assumed that the user is familiar with such an application.
Certain parameters are can also be congured via the BACnet
network (BAS). Parameters that can only be accessed
using the BACnet conguration menu are noted below. The
second part of this section, BACnet Commissioning and
Device Management, describes optional network testing and
verication tools available for the communication module.
The parameters listed below require conguration in order for
the communication module to properly integrate to the BACnet
network.
BACnet Device Properties
• Device Instance - must be set to a unique value on the
BACnet network
• Device Name - must be set to a unique value on the
BACnet network
• Location
• Units
• Description
BACnet MS/TP Settings
• MS/TP Baud Rate - must be set to match the speed
of the BACnet network. Valid values are 9600, 19200,
38400, or 76800. The baud rate must be set using the
BACnet conguration menu.
• MaxMasters - set to the highest address of a MS/TP
master on the network segment to reduce the MS/TP
token trafc and increase response time of the unit
controller. MaxMasters can be set from the BAS or from
the BACnet conguration menu.
• MAC Address / Address Switch - must be set according
to the BACnet network requirements. The MS/TP MAC
address can be set from the BAS or from the BACnet
conguration menu only when the physical address
switch (S3) is set to 255.
Accessing the BACnet Conguration
Menu
The BACnet communication module’s conguration menu is
accessed through the DB-9 serial connector on the module
itself. Any serial terminal device or application (such as
Windows HyperTerminal) can be used to view the menu and
change the conguration parameters.
Follow these steps to connect to the BACnet conguration
menu (Figure 1):
1. Verify that the terminal application communication
settings are set to: 19200 bps, 8-data bits, 1-stop bit, no
parity, and no ow control.
2. Use a null modem serial cross over cable to connect the
computer to the BACnet communication module.
3. Once connected, press the ‘Enter’ key to display the
menu shown in Figure 1.
4. Change the following parameters, if desired: Instance,
Name, Location, Description, MS/TP Baud Rate, and
Units.
5. Press ‘S’ to save the BACnet conguration settings.
6. Verify “Flash write – success” is shown for conguration
pages 1 and 2. Otherwise, save the settings again.
Figure 1: BACnet Conguration Menu
==================== Configuration Menu ====================
Daikin Applied – MTIIIUC_WSHP
BACnet FW HP0 v3.2 UnitApp HP0 v3.1
======= SW PN 2506908 ======================================
DEVICE
1) Instance ........... 3101127
2) Name ............... MTIIIUC_WSHP_3101127
3) Location ...........
4) Description .......
5) Units ................. English
MS/TP
6) Baudrate ............ 38400
7) MaxMasters ....... 127
M) MAC Address ... 127
TERMINAL
8) EIA-232 Baudrate ... 19200
B) Backup
R) Restore Configuration
S) Save settings
------------------------------------------------------------
Enter Selection: