ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 54 www.DaikinApplied.com
baCneT ConfIguraTIon and CommIssIonIng
BACnet Conguration
This section describes how to set BACnet parameters using
the BACnet communication module’s built-in conguration
menu (Figure 1). The BACnet conguration menu is accessed
using Microsoft Windows
®
HyperTerminal
®
or PuTTY. It is
assumed that the user is familiar with such an application.
Certain parameters are can also be congured via the BACnet
network (BAS). Parameters that can only be accessed
using the BACnet conguration menu are noted below. The
second part of this section, BACnet Commissioning and
Device Management, describes optional network testing and
verication tools available for the communication module.
The parameters listed below require conguration in order for
the communication module to properly integrate to the BACnet
network.
BACnet Device Properties
Device Instance - must be set to a unique value on the
BACnet network
Device Name - must be set to a unique value on the
BACnet network
Location
Units
Description
BACnet MS/TP Settings
MS/TP Baud Rate - must be set to match the speed
of the BACnet network. Valid values are 9600, 19200,
38400, or 76800. The baud rate must be set using the
BACnet conguration menu.
MaxMasters - set to the highest address of a MS/TP
master on the network segment to reduce the MS/TP
token trafc and increase response time of the unit
controller. MaxMasters can be set from the BAS or from
the BACnet conguration menu.
MAC Address / Address Switch - must be set according
to the BACnet network requirements. The MS/TP MAC
address can be set from the BAS or from the BACnet
conguration menu only when the physical address
switch (S3) is set to 255.
Accessing the BACnet Conguration
Menu
The BACnet communication module’s conguration menu is
accessed through the DB-9 serial connector on the module
itself. Any serial terminal device or application (such as
Windows HyperTerminal) can be used to view the menu and
change the conguration parameters.
Follow these steps to connect to the BACnet conguration
menu (Figure 1):
1. Verify that the terminal application communication
settings are set to: 19200 bps, 8-data bits, 1-stop bit, no
parity, and no ow control.
2. Use a null modem serial cross over cable to connect the
computer to the BACnet communication module.
3. Once connected, press the ‘Enter’ key to display the
menu shown in Figure 1.
4. Change the following parameters, if desired: Instance,
Name, Location, Description, MS/TP Baud Rate, and
Units.
5. Press ‘S’ to save the BACnet conguration settings.
6. Verify “Flash write – success” is shown for conguration
pages 1 and 2. Otherwise, save the settings again.
Figure 1: BACnet Conguration Menu
==================== Configuration Menu ====================
Daikin Applied MTIIIUC_WSHP
BACnet FW HP0 v3.2 UnitApp HP0 v3.1
======= SW PN 2506908 ======================================
DEVICE
1) Instance ........... 3101127
2) Name ............... MTIIIUC_WSHP_3101127
3) Location ...........
4) Description .......
5) Units ................. English
MS/TP
6) Baudrate ............ 38400
7) MaxMasters ....... 127
M) MAC Address ... 127
TERMINAL
8) EIA-232 Baudrate ... 19200
B) Backup
R) Restore Configuration
S) Save settings
------------------------------------------------------------
Enter Selection:

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals