ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 34 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 17: Network Conguration Properties Inputs (NCIs) - Ennity Single Stage Compressor, Continued
Point Name
lonWorks Variable
(NV Index
2
)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Conguration Property Inputs (NCIs)
Send Heartbeat nciSndHrtBt SCPTmaxSendTime
0 to 6553.4 sec
Default: 0
(Disabled)
No
Denes the maximum period of time that elapses before
the network variable outputs (NVOs) shown below are
automatically updated. Each NVO supported has a separate
timer associated with it. The BAS may be able to detect a
missing heartbeat from the unit controller to determine that
communication is lost and take corrective action. The value
of 0 disables the auto update feature.
Supported Variables
nvoDischAirTemp
nvoEffectOccup
nvoEffectSetpt
nvoFanSpeed
nvoLocalSpaceTmp
nvoSetpoint
nvoSetptShift
nvoSpaceTemp
nvoUnitStatus
Device Software
Identication
(Major Version)
nciDevMajVer SCPTdevMajVer 0 to 255 No
The software major version of the communication module
rmware.
Do not modify this conguration property.
Device Software
Identication
(Minor Version)
nciDevMinVer SCPTdevMinVer 0 to 255 No
The software minor version of the communication module
rmware.
Do not modify this conguration property.
Software Jumpers nciSoftJumpers UCPTsoftJumpers 16 Characters No
Sets the software jumper conguration. This property is not
implemented in unit controller software.
Unit Application
Identication
(Major Version)
nciUnitAppMajVer UCPTunitAppMajVer 0 to 255 No
The major version of the unit controller software.
Do not modify this conguration property.
Unit Application
Identication
(Minor Version)
nciUnitAppMinVer UCPTunitAppMinVer 0 to 255 No The minor version of the unit controller software.
Unoccupied Setpoint
Differential
nciUnoccDiff UCPTunOccDiff
2 to 10ºF
1.11 to 5.56ºC
Default:
2ºF / 1.11ºC
No
Sets the Unoccupied hysteresis that determines the Effective
OFF setpoints.
Interaction Rule
nciUnoccDiff < (unoccupied_cool – unoccupied_heat)
1. Analog Null (0x7FFF) is a discrete temperature value of 621.806ºF/327.67ºC. Its purpose is to indicate a sensor failure condition or when the unit controller is not
using that temperature value.
2. The Network Variable (NV) index number is a unique identier for certain LonWorks variables. Some BAS companies use this numeric value instead of text to
reference these variables. The NV index number can also be found in the XIF le.
3. After Receive Heartbeat is enabled, this variable reverts to the default (non-override) value if it is not refreshed often enough through a network command or if
communication is disabled (i.e. the device is disabled or is ofine).

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals