EasyManua.ls Logo

Daikin RCS - DPS;DPH Expansion Module D I;O

Daikin RCS
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 12: DPS/DPH Expansion Module D I/O
I/O Cong. Code Condition
Expansion Module D Pos. 1=3or4
Analog Inputs — NTC
# Point Comments Cong. Code Condition
AI 1 Indoor Refrigerant Temperature (IRT) 10K Thermistor (STD) 1 = 4 & 30 = 3, 4, 5 or 6
AI 2
Outdoor Refrigerant Temperature
(ORT)
10K Thermistor (STD) 1 = 4 & 30 = 3, 4, 5 or 6
AI 3
Outdoor Coil Defrost Temperature
(DFT)
10K Thermistor (STD) 1 = 4 & 30 = 3, 4, 5 or 6
Universal Inputs/Outputs
# DI AI DO AO Point Comments Cong. Code Condition
X 1 X
Compressor Suction Pressure Sensor
(PTS)
0.5–4.5 VDC 0–350 psi
X 2 X
Compressor Discharge Pressure
Sensor (PTD)
0.5–4.5 VDC 0–700 psi
X 3 X
INV Compressor Discharge Line
Refrigerant Temperature (DRT1)
100K Thermistor (HT)
X 4 X
STD3 Compressor Discharge Line
Refrigerant Temperature (DRT3)
100K Thermistor (HT) 4 = M
X 5 X Heating Valve
Gas 2–10 VDC HW/STM 2–10 VDC
SCR 0–10 VDC
10 = 5, 6 or 7
X 6 X
Compressor Suction Line Refrigerant
Temperature (SRT)
10K Thermistor (STD)
X 7 X
Outdoor Coil Defrost Temperature
(DFT)
10K Thermistor (STD) 1 = 4 & 30 = 1 or 2
X 7 X INV Compressor Body Temperature 100K Thermistor (HT) 24, 25, 26 = 0, 1, 5
X 8 X Reheat Output 0–10 VDC 28 = 2
X 9 X Supply Temp Leaving Wheel 10K Thermistor (STD) 20 > 0 & 30 = 3, 4, 5 or 6
X 10 X Exhaust Temp Leaving Wheel 10K Thermistor (STD) 20 > 0 & 30 = 3, 4, 5 or 6
X 11 X OA Flow 0–10 VDC or 4–20 mA
8 = 1, 2, 3, 5,6 or 7 & 9 = 6 &
30 = 3, 4, 5 or 6
X 12 X Freezestat Switch 0-5 VDC 10 =5 & 8 = 8 or 9 & 30 = 3, 4, 5 or 6
Digital Input — 115V-230V
# Point Comments Cong. Code Condition
DI Freezestat Switch 115 VAC Input 10 = 5 & 8 = 3 or 6
DI OAD End Switch Input 115 VAC Input 8 = 8 or 9
Digital Outputs — Relay (SPST, Normally Open, 230 VAC 3 Amp)
# Point Comments Cong. Code Condition
DO 1 INV Board Power Up
DO 2
Refrigerant Receiver Gas Line
Solenoid Valve (SVR)
1 = 4
DO 3 Bypass Solenoid Valve (SVB)
DO 4 4 Way Reversing Valve (4WV) 1 = 4
Digital Outputs — Triac (24 VAC, 0.5 Amp)
# Point Comments Cong. Code Condition
DO 5 Bypass Damper CLOSED Energy Recovery 20 > 0 & 8 = 3 or 6 & 30 = 3, 4, 5 or 6
DO 6 Bypass Damper OPEN Energy Recovery 20 > 0 & 8 = 3 or 6 & 30 = 3, 4, 5 or 6
IM 919-3 • MICROTECH III CONTROLLER 22 www.DaikinApplied.com
ConTroller InpuTs/ouTpuTs

Related product manuals