EasyManua.ls Logo

Daikin Siesta - Checking Refrigerant Piping

Daikin Siesta
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3Installation
Installationmanual
6
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855281–2014.08
3.2.2 Todetermineifoiltrapsarerequired
Ifoilflowsbackintotheoutdoorunit'scompressor,thismightcause
liquidcompressionordeteriorationofoilreturn.Oiltrapsintherising
gaspipingcanpreventthis.
If Then
Theindoorunitisinstalled
higherthantheoutdoor
unit
Installanoiltrapevery10m(height
difference).
a
b
10 m
aRisinggaspipingwithoiltrap
bLiquidpiping
Theoutdoorunitis
installedhigherthanthe
indoorunit
OiltrapsareNOTrequired.
3.3 Checkingtherefrigerantpiping
3.3.1 Checkingrefrigerantpiping:Setup
a
c
f
b d e
R410A
a Pressuregauge
b Nitrogen
c Refrigerant
d Weighingmachine
e Vacuumpump
f Stopvalve
3.3.2 Tocheckforleaks
NOTICE
DoNOTexceedtheunit'smaximumworkingpressure(see
"PSHigh"ontheunitnameplate).
NOTICE
Make sure to use a recommended bubble test solution
from your wholesaler. Do not use soap water, which may
causecrackingofflarenuts(soapwatermaycontainsalt,
which absorbs moisture that will freeze when the piping
gets cold), and/or lead to corrosion of flared joints (soap
water may contain ammonia which causes a corrosive
effectbetweenthebrassflarenutandthecopperflare.
1 Chargethesystemwithnitrogengasuptoagaugepressureof
at least 200 kPa (2 bar). It is recommended to pressurize to
3000kPa(30bar)inordertodetectsmallleaks.
2 Check for leaks by applying the bubble test solution to all
connections.
3 Dischargeallnitrogengas.
3.3.3 Toperformvacuumdrying
1 Vacuumthesystemuntilthepressureonthemanifoldindicates
−0.1MPa(−1bar).
2 Leaveasisfor45minutesandcheckthepressure:
Ifthepressure… Then…
Doesnotchange Thereisnomoistureinthe
system.Thisprocedureis
finished.
Increases Thereismoistureinthe
system.Gotothenextstep.
3 Evacuateforat least 2 hours to a pressure on the manifold of
−0.1MPa(−1bar).
4 After turning OFF the pump, check the pressure for at least
1hour.
5 IfyoudoNOTreachthetargetvacuumorcannotmaintainthe
vacuumfor1hour,dothefollowing:
Checkforleaksagain.
Performvacuumdryingagain.
NOTICE
Make sure to open the stop valves after installing the
refrigerantpipingandperformingvacuum drying. Running
the system with the stop valves closed may break the
compressor.
3.4 Chargingrefrigerant
3.4.1 Todeterminetheadditionalrefrigerant
amount
Todetermineifaddingadditionalrefrigerantisnecessary
If Then
L1≤30m(chargelesslength) Youdonothavetoadd
additionalrefrigerant.
L1>30m Youmustaddadditional
refrigerant.
Forfutureservicing,encirclethe
selectedamountinthetables
below.
INFORMATION
Pipinglengthistheonewaylengthofliquidpiping.
Todeterminetheadditionalrefrigerantamount(Rinkg)
L1 (m)
30~40m 40~50m
R: 0.5kg 1.0kg
3.4.2 Todeterminethecompleterecharge
amount
Model
L1 (m)
5~10 10~20 20~30 30~40 40~50
AZQS100+125 1.9 2.4 2.9 3.4 3.9
AZQS140 3.0 3.5 4.0 4.5 5.0

Related product manuals