Si39-303 Appendix
General Information 113
7.4 Refrigerant branch kit selection
7.4.1 How to select the refnet joint
!
When using refnet joints at the first branch counted from the outdoor unit side.
Choose from the following table in accordance with the capacity of the outdoor unit.
!
For refnet joints other than the first branch, select the proper branch kit model based on the
total capacity index of downstream indoor units.
*Example of downstream indoor units
1. example in case of refnet joint C; indoor units 3 + 4 + 5 + 6 + 7 + 8,
2. example in case of refnet joint B indoor units 7 + 8
example in case of refnet joint header; indoor units 1 + 2 + 3 + 4 + 5 + 6
3. example in the case of refnet header; indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Refrigerant branch kits can only be
used with R410A.
Outdoor unit capacity type Refrigerant branch kit name
RXYQ5 type KHRP26M22T
RXYQ8, 10type KHRP26M33T
RXYQ12 ~ 22 type KHRP26M72T
RXYQ24 type ~ KHRP26M73T + KHRP73TP
Indoor capacity index Refrigerant branch kit name
< 200 KHRP26M22T
200
≤
X < 290 KHRP26M33T
290
≤
X < 640 KHRP26M72T
640 < KHRP26M73T + KHRP73TP