Model RXYQ5MY1B RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B RXYQ14MY1B RXYQ16MY1B
Power supply
Phase 3N
~
3N
~
3N
~
3N
~
3N
~
3N
~
Frequency Hz 50 50 50 50 50 50
Voltage V 380
-
415 380
-
415 380
-
415 380-415 380-415 380-415
Voltage torerance % ±10 ±10 ±10 ±10 ±10 ±10
Recommended fuses A 20 30 30 30 40 40
Compressor
Phase 3
~
3
~
3
~
3
~
3
~
3
~
Frequency Hz 50 50 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415 380-415 380-415
Nominal running
current
A 6.1-6.7
(2.8-3.1)+
(7.3-7.9)
(5.8-6.3)+
(7.7-8.4)
(7.7-8.4)+
(7.8-8.5)
(4.4-4.8)+
(8.2-8.9)+
(8.2-8.9)
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
Control and
fan motor
Type
Voltage V 220-240 220-240 220-240 220-240 220-240 220-240
Nominal
running current
A 0.3 0.7 0.7 1.1 1.1 1.1
Model RXYQ18MY1B RXYQ20MY1B RXYQ22MY1B RXYQ24MY1B RXYQ26MY1B RXYQ28MY1B
Power supply
Phase 3N
~
3N
~
3N
~
3N
~
3N
~
3N
~
Frequency Hz 50 50 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415 380-415 380-415
Voltage torerance % ±10 ±10 ±10 ±10 ±10 ±10
Recommended fuses A 50 50 50 60 60 70
Compressor
Phase 3
~
3
~
3
~
3
~
3
~
3
~
Frequency Hz 50 50 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415 380-415 380-415
Nominal running
current
A
(2.8-3.1)+
(7.3-7.9)+
(5.8-6.3)+
(7.7-8.4)
(5.8-6.3)+
(7.7-8.4)+
(5.8-6.3)+
(7.7-8.4)
(5.8-6.3)+
(7.7-8.4)+
(7.7-8.4)+
(7.8-8.5)
(5.8-6.3)+
(7.7-8.4)+
(4.4-4.8)+
(8.2-8.9)+
(8.2-8.9)
(5.8-6.3)+
(7.7-8.4)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(7.7-8.4)+
(7.8-8.5)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
Control and
fan motor
Type
Voltage V 220-240 220-240 220-240 220-240 220-240 220-240
Nominal
running current
A 0.7×2 0.7×2 0.7+1.1 0.7+1.1 0.7+1.1 1.1×2
Model RXYQ30MY1B RXYQ32MY1B RXYQ34MY1B RXYQ36MY1B RXYQ38MY1B RXYQ40MY1B
Power supply
Phase 3N
~
3N
~
3N
~
3N
~
3N
~
3N
~
Frequency Hz 50 50 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415 380-415 380-415
Voltage torerance % ±10 ±10 ±10 ±10 ±10 ±10
Recommended fuses A 70 70 90 90 90 100
Compressor
Phase 3
~
3
~
3
~
3
~
3
~
3
~
Frequency Hz 50 50 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415 380-415 380-415
Nominal running
current
A
(4.4-4.8)+
(8.2-8.9)+
(8.2-8.9)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(5.8-6.3)+
(7.7-8.4)+
(5.8-6.3)+
(7.7-8.4)+
(4.4-4.8)+
(8.2-8.9)+
(8.2-8.9)
(5.8-6.3)+
(7.7-8.4)+
(5.8-6.3)+
(7.7-8.4)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(5.8-6.3)+
(7.7-8.4)+
(7.7-8.4)+
(7.8-8.5)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(5.8-6.3)+
(7.7-8.4)+
(4.4-4.8)+
(8.2-8.9)+
(8.2-8.9)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
Control and
fan motor
Type
Voltage V 220-240 220-240 220-240 220-240 220-240 220-240
Nominal
running current
A 1.1×2 1.1×2 1.1+0.7×2 1.1+0.7×2 0.7+1.1×2 0.7+1.1×2
Model RXYQ42MY1B RXYQ44MY1B RXYQ46MY1B RXYQ48MY1B
Power supply
Phase 3N
~
3N
~
3N
~
3N
~
Frequency Hz 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415
Voltage torerance % ±10 ±10 ±10 ±10
Recommended fuses A 100 100 110 110
Compressor
Phase 3
~
3
~
3
~
3
~
Frequency Hz 50 50 50 50
Voltage V 380-415 380-415 380-415 380-415
Nominal running
current
A
(5.8-6.3)+
(7.7-8.4)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(7.7-8.4)+
(7.8-8.5)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(4.4-4.8)+
(8.2-8.9)+
(8.2-8.9)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)+
(5.7-6.2)+
(8.4-9.2)+
(8.4-9.2)
Control and
fan motor
Type
Voltage V 220-240 220-240 220-240 220-240
Nominal
running current
A 0.7+1.1×2 1.1×3 1.1×3 1.1×3