Si39-303 Unpacking and Placing the Unit
Installation Manual 165
5. Unpacking and Placing the Unit
!
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and
noise.
!
Secure the unit to its base using foundation bolts. (Use four commercially available M12-
type foundation bolts, nuts, and washers.)
!
The foundation bolts should be inserted 20 mm.
!
Make sure the base under the unit extended more than 765mm behind the unit.
!
The height of the base should be at least 150mm from the floor.
!
The unit must be installed on a solid longitudinal foundation (steel beam frame
or concrete) as indicated in figure below.
1.Foundation bolt point (
φ
15 dia. : 4 positions)
2.Depth of product
3.Shape of indoor units support leg and foundation bolt positions
Do not use stands to support the corners
Caution 1. Prepare a water drainage channel around the foundation to drain waste water from around
the unit.
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities
first.
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of
150mm under the unit in order to prevent infiltration of water coming from under the unit.
[Precaution]
!
When installing on a roof, make sure the roof floor is strong enough and be sure to water-
proof all work.
!
Make sure the area around the machine drains properly by setting up drainage grooves
around the foundation.
(Drain water is sometimes discharged from the outdoor unit when it is running.)
!
Block all gaps in the holes for passing out piping and wiring using sealing material (locally
procured). (Small animals may enter the machine.)
Model A B
Q5 type 635 497
Q8 · 10 type 930 792
Q12 · 14 · 16 type 1240 1102
20
722-737
8080
765
A
B
1
2
3
Do not use stands to
support the corners.