Si39-303 Product Outline
General Information 7
Connectable indoor unit
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
!
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
!
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
Type Model Name Power Supply
Ceiling mounted
cassette type
(Double flow)
FXCQ 20M 25M 32M 40M 50M 63M 80M — 125M — —
VE
Ceiling mounted
cassette type
(Multi flow)
600×600
FXZQ 20M 25M 32M 40M 50M — — — — — —
Ceiling mounted
cassette type
(Multi flow)
FXFQ — 25M 32M 40M 50M 63M 80M 100M 125M — —
Ceiling mounted
cassette corner
FXKQ — 25M 32M 40M — 63M — — — — —
Ceiling mounted
built-in type
FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M — —
Ceiling mounted
duct type
FXMQ — — — 40M 50M 63M 80M 100M 125M 200M 250M
Ceiling
suspended type
FXHQ — — 32M — — 63M — 100M — — —
Wall mounted
type
FXAQ 20M 25M 32M 40M 50M 63M — — — — —
Floor standing
type
FXLQ 20M 25M 32M 40M 50M 63M — — — — —
Concealed Floor
standing type
FXNQ 20M 25M 32M 40M 50M 63M — — — — —
New refrigerant model code P20
type
P25
type
P32
type
P40
type
P50
type
P63
type
P80
type
P100
type
P125
type
P200
type
P250
type
Selecting model capacity 2.2
kW
2.8
kW
3.5
kW
4.5
kW
5.6
kW
7.0
kW
9.0
kW
11.2
kW
14.0
kW
22.4
kW
28.0
kW
Equivalent output 0.8HP 1HP
1.25HP
1.6HP 2.0HP 2.5HP 3.2HP 4HP 5HP 8HP 10HP