Appendix Si39-303
130 General Information
Before turning on the power
Inspection item
Inspection method
Standard (guideline) Measurement values
Decision
Breaker capacity Visual inspection Specified capacity G NG
Refrigerant piping system
Gas detector No leaks G NG
Heat exchanger Visual inspection
No clogging or damage
G NG
Terminal connection section
Screwdriver, etc. No looseness G NG
Fan motor electrical insulation
500-V megatester
1 M
or more M
Compressor electrical insulation
500-V megatester
1 M
or more
Installation Visual inspection Short circuit, etc. G NG
Refrigerant piping system
Gas detector No leaks G NG
Heat exchanger Visual inspection
No clogging or damage
G NG
Terminal connection section
Screwdriver, etc. No looseness G NG
Fan motor electrical insulation
500-V megatester
1 M
or more M
Compressor electrical insulation
500-V megatester
1 M
or more
Installation Visual inspection Short circuit, etc. G NG
Refrigerant piping system
Gas detector No leaks G NG
Heat exchanger Visual inspection
No clogging or damage
G NG
Terminal connection section
Screwdriver, etc. No looseness G NG
Fan motor electrical insulation
500-V megatester
1 M
or more M
Compressor electrical insulation
500-V megatester
1 M
or more
Installation Visual inspection Short circuit, etc. G NG
Indoor
unit
Refrigerant
system
Gas detector No leaks
Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG
Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG
Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG
Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG
Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG
Room 21 G NG Room 22 G NG Room 23 G NG Room 24 G NG
Room 25 G NG Room 26 G NG Room 27 G NG Room 28 G NG
Room 29 G NG Room 30 G NG Room 31 G NG Room 32 G NG
Room 33 G NG Room 34 G NG Room 35 G NG Room 36 G NG
Room 37 G NG Room 38 G NG Room 39 G NG Room 40 G NG
Air filter
Visual
inspection
No clogging or
damage
Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG
Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG
Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG
Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG
Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG
Room 21 G NG Room 22 G NG Room 23 G NG Room 24 G NG
Room 25 G NG Room 26 G NG Room 27 G NG Room 28 G NG
Room 29 G NG Room 30 G NG Room 31 G NG Room 32 G NG
Room 33 G NG Room 34 G NG Room 35 G NG Room 36 G NG
Room 37 G NG Room 38 G NG Room 39 G NG Room 40 G NG
Heat exchanger
Visual
inspection
No clogging or
damage
Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG
Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG
Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG
Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG
Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG
Room 21 G NG Room 22 G NG Room 23 G NG Room 24 G NG
Room 25 G NG Room 26 G NG Room 27 G NG Room 28 G NG
Room 29 G NG Room 30 G NG Room 31 G NG Room 32 G NG
Room 33 G NG Room 34 G NG Room 35 G NG Room 36 G NG
Room 37 G NG Room 38 G NG Room 39 G NG Room 40 G NG
System name
Outdoor unit 1
INV M
STD1 M
STD2 M
Outdoor unit 2
Outdoor unit 3