Installation Si39-303
42 General Information
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
!
Remove the electric parts box lid, connect a power supply and remote controller to the terminals. (Refer
to the How to CONNECT WIRINGS (Refer to Installation Manual))
Next, press the inspection/test operation button ” on the remote controller. The unit will engage
the test operation mode. Press the operation mode selector button until selecting FAN
OPERATION ”. Then, press the ON/OFF button “ ”. The indoor unit fan and drain pump will
start up. Check that the water has drained from the unit. Press to go back to the first mode.
!
You can check whether drainage is satisfactory or not by removing the access opening lid and checking
the water level of the drain pan through the access opening.
!
Be careful when doing so because the fan is turning at the same time.