Test Operation Si39-303
68 General Information
4.4.1.2 Wireless Remote Controller - Indoor Unit
BRC7C type
1. When in the normal mode, push the button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the button.
3. Pushing the button, select the first code No.
4. Pushing the button, select the second code No.
5. Push the timer button and check the settings.
6. Push the button to return to the normal mode.
(Example)
When setting the filter sign time to Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0and setting position No. to “02”.