5 Installation
Installation manual
32
RWEQ96~432TAYCU
VRV W T-Series water-cooled system air conditioner
4P540122-1B – 2018.11
5.8.4 To route and fix the transmission wiring
Transmission wiring can be routed through the front side only. Fix it
to the upper mounting hole.
F1 F1F2 F2 Q1 Q2
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
A
A1P
A
Fix to the indicated plastic brackets (factory installed).
5.8.5 To connect the transmission wiring
The wiring from the indoor units must be connected to the F1/F2
(In-Out) terminals on the PCB in the outside unit.
Tightening torque for the transmission wiring terminal screws:
Screw size Tightening torque
M3.5 (A1P) 0.59~0.71 ft·lbf (0.8~0.97 N·m)
In case of heat recovery mode
F1 F2 F1 F2 Q1 Q2
F1 F1F2 F2 Q1Q2
g
e
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
A1P
Q1 Q2
A1P
Q1 Q2
A1P
a b c
d
f
F1 F2 F1 F2 F1 F2 F1 F2
TO IN/D
UNIT
TO OUT/D
UNIT
TO IN/D
UNIT
TO OUT/D
UNIT
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 F1 F2
j
ii
hh
e
a Unit A (main outside unit)
b Unit B (sub outside unit)
c Unit C (sub outside unit)
d Outside unit PCB (A1P)
e Main/sub transmission (Q1/Q2)
f Outside/indoor transmission (F1/F2)
g Outside unit/other system transmission (F1/F2)
h Branch selector unit
i Indoor unit
j Cooling-only VRV indoor unit
In case of heat pump mode
F1 F1F2 F2 Q1 Q2
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 Q1 Q2 Q1 Q2
A1P
e
Q1 Q2
a
h
i
g
f
cb d
e f
a Outside unit PCB (A1P)
b Unit A (main outside unit)
c Unit B (sub outside unit)
d Unit C (sub outside unit)
e Outside unit/other system transmission (F1/F2)
f Outside-outside unit transmission (Q1/Q2)
g Indoor unit
h Use the conductor of sheathed wire (2 wire) (no polarity)
i Terminal board (field supply)
▪ Theinterconnectingwiringbetweentheoutsideunitsinthesame
piping system must be connected to the Q1/Q2 (Out Multi)
terminals. Connecting the wires to the F1/F2 terminals results in
system malfunction.
▪ ThewiringfortheothersystemsmustbeconnectedtotheF1/F2
(Out-Out) terminals of the PCB in the outside unit to which the
interconnecting wiring for the indoor units is connected.
▪ The base unit is the outside unit to which the interconnecting
wiring for the indoor units is connected.
5.8.6 To finish the transmission wiring
After installing the transmission wires inside the unit, wrap them
along with the on-site refrigerant pipes using finishing tape, as
shown in figure below.
b
a
f
d
f
e
f
a Liquidpipe
b Gas pipe
c Finishing tape
d High pressure/low pressure gas pipe
e Transmission wiring (F1/F2)
f Insulator
5.8.7 To route and fix the power supply
NOTE
When routing ground wires, secure clearance of 1 inch
(25.4 mm) or more away from compressor lead wires.
Failure to observe this instruction properly may adversely
affect correct operation of other units connected to the
same ground.