11 Technical data
Installation manual
48
RWEQ96~432TAYCU
VRV W T-Series water-cooled system air conditioner
4P540122-1B – 2018.11
11 Technical data
11.1 Overview: Technical data
This chapter contains information about:
▪ Servicespace
▪ Pipingdiagram
▪ Wiringdiagram
11.2 Service space: Outside unit
Make sure the space around the unit is adequate for servicing and
the minimum space for ventilation is available (refer to the figure
below).
a a
b
b
b
b
(*1)
cc
b
b
F
d
(*2)
a ≥19-11/16inch(500mm)
b ≥13/16inch(20mm)
c ≥35-7/16inch(900mm)
d ≥11-13/16inch(300mm)
F Front side
*1 This ventilation space is necessary when heat rejection
cancellation is not active.
*2 This space is necessary when refrigerant piping is connected to
the top of the unit.
INFORMATION
Further specifications can be found in the technical
engineering data.