OMM 1130-2 21
Setpoints
The following parameters are remembered during power off, are factory set to the Default value, and can be
adjusted to any value in the Range column.
The PW (password) column indicates the password level that must be active in order to change the setpoint.
Passwords are as follows:
O = Operator [0100] M = Manager [2001]
Table 7, Setpoints (setpoints with * are set at Daikin Applied factory)
Description Default Range PW
*Unit Mode (R22, R407C, R410A Cool Cool, Cool w/Glycol, Ice w/Glycol, Test O
Unit Mode (R134a) Cool Cool, Cool w/Glycol, Heat, Test
Keypad, Network, Switches
*Available Modes (R22,R407C,R410A) Cool
Cool, Cool w/Glycol, Cool/Ice w/Glycol
M
*Available Modes (R134a) Cool
Test, Cool, Cool w/Glycol, Cool/Heat, COOL/HEAT
w/Glycol, Heat w/Glycol,
M
Evap LWT
44. 0 °F
Without Glycol: 40.0 to 60.0°F
40.0 to 85.0°F (R134a Only)
With Glycol: 20.0 to 60.0°F (R22,R407C)
10.0 to 60.0°F (R410A)
°
O
Ice LWT
°
°
O
Heat LWT (R134a only)
°
°
O
°
°
°
°
Stop Delta T
0.5 °F 0 to 3.0 °F
O
°
°
Evap Pump
(Refrigerant = R410a,R134a)
#1 Only
#1 Only, #2 Only, Auto, #1 Prim,
#2 Prim
M
Cond Delta T (R134a only)
°
°
Cond Pump Recirculate Timer
30 15 to 90 seconds M
Cond Pump
(Water-cooled=Yes & Ref=R410A or R134a
#1 Only #1 Only, #2 Only, Auto, #1 Prim, #2 Prim M
Low Ambient Lockout(Water-Cooled = No)
35.0 °F
35 to 70 °F
If Speedtrol = Yes
-2.0 to70.0°F (R22,R407C)
-10.0 to 70.0 (R410A)
N/A (R134a)
M
Ice Time Delay 12 hrs 1 to 23 hrs M
1200,2400,4800,9600,19200
None, 4-20mA, [Return( Refrig = R134a only)]
Cooling Start Reset Delta T 10 ºF 0 to 16 ºF (Refrig = R134a only) O
# of Compressors
(Refrig = R410A or R134a to select 6)
4 4, 6 M
Stage Up Delay 240 sec 90 to 480 seconds M